FAULT FINDING AND DIAGNOSIS
6 720 644 744b (2011/08)
58
7 FAULT FINDING AND DIAGNOSIS
7.1 FAULT FINDING
The electronic control system for this boiler
incorporates a blue central indicator. This normally
confirms the permanent mains supply but, by flashing at
different rates during a fault, provides a guide to the
cause as listed.
This fault finding system assumes that the appliance has
been operating normally until the time of failure (i.e. not
a first installation error).
PRELIMINARY CHECKS : Preliminary electrical system
checks are the first electrical checks to be carried out
during a fault-finding procedure. On completion of the
Service/Fault-Finding task which has required the
breaking and remaking of electrical connections, check:
(a) EARTH CONTINUITY,
(b) SHORT CIRCUIT CHECK,
(c) POLARITY and
(d) RESISTANCE TO EARTH.
This fault finding information is for guidance
only. Worcester cannot be held responsible
for costs incurred by persons not deemed to
be competent.
Blue light
indication
Fault Possible solution/check
No light No power at
control board
Permanent mains supply to boiler.
Boiler mains switch ON.
Fuse F1 - 2A Slow blow.
Fuse F2 - 1.25A Anti-surge.
Transformer (both coils below 100 Ω.
Otherwise replace control board.
Light ON Boiler ON but not
operating during
demand
Live demand at ST2 terminal L
R
- is there a demand?
Manual bypass is open.
If CH is working check HW controls
If HW is working check CH controls (i.e. external diverter valve,
frost stat, room stat/programmer.
Otherwise replace board.
Slow flash
(mostly off,
flashes on)
Ignition lockout B Gas present and at correct pressure?
B Gas valve
Check that there is 35V d.c. to each solenoid
Check the resistance of each solenoid:
Top solenoid = 380 Ω ± 10% (342 - 418 Ω)
Bottom solenoid = 190 Ω ± 10% (171 - 209 Ω)
B Combustion CO
2
level.
B Flue condition.
Blocked flue?
B Blocked condensate pipe or frozen condensate.
B Gas valve adjustment.
B Ignition electrodes/harness/connections.
Check for condition and resistance of leads
(approximately 2100 Ω)
B Otherwise replace control board
Tab. 24 Fault finding