Worcester Greenstar Ri Manuel de service Page 10

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 21
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 9
1918
Plume management terminal positioning
Door
Balcony
Boundary
Drainpipe
3
2
4
5
6
1
200
200
100
200
200
200
300
300
300
300
1,200
150
150
150
150
150
600
Window
Window
25
25
Window
±45°
Flue exhaust
outlet
Air intake
7
Plume management deflector:
180°
±80°
8
All measurements in millimetres
Note
All measurements are the minimum clearances required.
Terminals must be positioned so to avoid combustion
products entering the building.
Support the flue at approximately one metre intervals and at
a change of direction, use suitable brackets and fittings.
Key to illustration
1. 600mm distance to a boundary or surface facing a boundary,
unless it will cause a nuisance. BS 5440: Part 1 recommends
that care is taken when siting terminals in relation to
boundaries.
2. Internal/external corners. The air intake clearance can be
reduced to 150mm providing the flue exhaust outlet has a
300mm clearance.
3. The flue cannot be lower than 1,000mm from the top of the
light well due to the build up of combustion products.
4. 1,200mm between air intake and facing terminal.
5. Clearance no less than 200mm from the lowest point of the
balcony or overhang.
Installations in car ports are not recommended.
6. 1,200mm from an opening in a car port on the same wall
i.e. door or window leading into dwelling.
7. Using a Plume Management Kit the air intake measurement can
be reduced to 150mm providing the flue exhaust outlet has a
300mm clearance. Plume kits running horizontally must have a
10º fall back to the boiler for proper disposal of condensate.
For details on specific lengths see relevant boiler Technical &
Specification information.
8. This feature allows some basic plume re-direction options on a
standard telescopic horizontal flue terminal. 300mm minimum
clearances to a opening e.g. window. However the minimum
clearance to an opening in direction that the plume management
is facing, must be increased to 1,500mm. Where the flue is less
than 150mm to a drain pipe and plume re-direction is used the
deflector should not be directed towards the drainpipe.
External
rain water
pipe into
foul water
External
air break
Air gap
Syphon
trap
Pipe work
transition
Insulate
& increase
pipe size
68mm dia. PVCu
strap on fitting
Condensate
pump
Fig. 4 Disposal into a rainwater down pipe
25mm min.
Syphon
trap
Insulate
& increase
pipe size
Pipe work
transition
Fig. 5 External disposal
Pipe work
transition
500mm min.
25mm min.
400mm
min.
Syphon
trap
Bottom of sealed tube
Limestone chippings
100mm
dia. min.
plastic
pipe
100mm dia.
Insulate
& increase
pipe size
Drainage
holes
100mm
dia. min.
plastic pipe
25mm
25mm
50mm
25mm
300mm
Drainage
holes
12mm dia.
Fig. 6 Soak away
25mm min.
Insulate
& increase
pipe size
Condensate
pump
Syphon
trap
Pipe work
transition
Fig. 7 Condensate pump to external disposal
External condensate pipe work
Vue de la page 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 20 21

Commentaires sur ces manuels

Pas de commentaire