CONDENSATE CONNECTION:
Never terminate or discharge into any open
source, including; sink, bath, shower, bidet,
toilet etc.
NOTE: Any external condensate pipework
should be protected with weather
resistant insulation to help prevent
freezing.
Ensure that the condensate drain is 22mm
diameter plastic pipe. It must fall at least
50mm per metre towards the outlet
NOTE: Do not use solvents, adhesive or
lubricant when pushing the pipe
onto the rubber connector.
A 22mm adaptor (A) and sealing washer (B)
is supplied in the fitting pack
CONDENSATE CONNECTIONS
A
B
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR Ri
8 716 115 168a (06/2008)
23
CONDENSATE, GAS & WATER
CONNECTIONS
INSTALLATION
Mains cable Inlet