Worcester Greenstar Ri Manuel d'instructions Page 52

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 51
MAIN FUNCTION
NO
YES
PERMANENT
MAIN SUPPLY
TO BOILER
BOILER
DEMAND
FROM
SYSTEM
Fan to
start
speed.
Pump ON.
Prepurge
then ignition
spark
4 seconds
BLUE
LIGHT
ON
BURNER
LIT?
GREEN
FLAME
LIGHT
ON
Fan run
10 seconds
then re-spark
5th
attempt?
LOCKOUT
Stabilisation
then fan low
45 seconds
Fan (& gas)
modulation
to achieve
set
temperature
(35-82°C)
END OF
BOILER
DEMAND
Gas valve
OFF
Pump run 3
minutes
Fan run 30
seconds
Over temperature shut-
down if water tempera-
ture is 5°C above set
value.
Fan overrun
30 seconds
3 minute wait
Boiler temperature
below 8°C
Run autofroststat
function
PROTECTION SYSTEMS
Pump antiseize
Pump run 5 seconds
every 24hrs
NO
YES
MAIN FUNCTION
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR Ri
8 716 115 168a (06/2008)
51
50
FAULT FINDING
& DIAGRAMS